Internal Design Temperatures

Ctrl+D to bookmark this tool

Recommended indoor temperature ranges for heating and cooling design from CIBSE Guide A. Quick reference for building services engineers.

Data from CIBSE Guide A (2015), Table 1.5. Always verify against current editions and project-specific requirements.

Winter Heating Design Temperatures

CIBSE Guide A, Table 1.5 — Recommended indoor environmental conditions
Space Type Operative Temp (°C) Resultant Temp (°C) Notes
Office (general) 21–23 22 Sedentary occupancy
Office (open plan) 21–23 22 —
Classroom 19–21 20 Active occupancy
Lecture theatre 19–21 20 —
Hospital ward 22–24 23 Patients resting
Operating theatre 18–22 20 Varies with surgical team preference
Consulting / exam room 22–24 23 —
Hotel bedroom 19–21 20 Guest comfort
Hotel lobby / reception 19–21 20 —
Retail (general) 19–21 20 Browsing / light activity
Retail (department store) 19–21 20 —
Restaurant / dining 21–23 22 Seated
Kitchen (commercial) 16–18 17 High internal gains
Sports hall 13–16 14 Active use
Swimming pool hall 23–26 24 1°C above pool water temp
Car park (heated) 5–10 7 Frost protection only
Plant room 10–16 12 Equipment protection
Corridor / circulation 19–21 20 —
Toilet / WC 19–21 20 —
Warehouse 12–16 14 Depends on contents
Residential living room 21–23 22 BS EN 12831
Residential bedroom 17–19 18 BS EN 12831
Residential bathroom 22–24 23 —

Operative temperature accounts for both air temperature and mean radiant temperature. In most well-insulated buildings, operative and air temperature are within 1°C.

Summer Cooling Design Temperatures

CIBSE Guide A, Table 1.5

Summer design temperatures define the maximum acceptable indoor temperature during peak cooling conditions. These are NOT the setpoint — they are the upper limit used for plant sizing.

Space Type Max Summer Temp (°C) Notes
Office (general) 25–27 TM52 overheating criteria also apply
Classroom 25–28 BB101 overheating criteria apply
Hospital ward 25–28 HTM 03-01 may set tighter limits
Retail 25–27 —
Hotel bedroom 25–27 —

Summer design temperatures should be used alongside overheating assessments (CIBSE TM52 for non-domestic, TM59 for domestic). Meeting the design temperature alone does not guarantee compliance with Part O.

External Design Temperatures (UK)

CIBSE Guide A, Table 2.x — UK external design conditions
Location Winter design (°C) Summer design dry bulb (°C) Notes
London (Heathrow) -4.2 31.3 Most commonly used
Birmingham -5.2 29.4 —
Manchester -4.8 28.0 —
Edinburgh -5.9 26.3 —
Belfast -3.7 25.4 —
Cardiff -3.9 28.2 —
Glasgow -6.0 26.0 —

Winter design temperature is the 99.6% cold design condition. Summer design dry bulb is the 1% exceeded condition. Values from CIBSE Guide A. Use CIBSE weather files for dynamic simulation.

Key concept: The winter design temperature determines your heating load. The difference between internal design temp and external design temp (ΔT) drives heat loss calculations: Q = U × A × ΔT. For a London office: ΔT = 22 - (-4.2) = 26.2 K

MEP Desk uses these design temperatures in its calculation engine — enter room data and assumptions, and heat loss is calculated automatically.